Constant Air Volume Dampers
SKC-C
Constant Air Volume Damper For Circular Duct - High Pressure
SKC-C is a self-adjustable damper, independent of external energy sources. It is preset by the installer to maintain a specific air volume in cfm or m3/h. The damper will then auto-adjust itself to maintain the desired volume of air while performing within a pressure range between 0.2 and 4 in.w.g. (between 50 and 1,000 Pa).
- Air volume preset by mean of a knob, from outside of the duct
- The damper will auto-adjust itself to maintain the desired volume of air while performing within the pressure range
- Housing is constructed from galvanized steel
- Available for 4″, 5″, 6″, 8″, 10″, 12″, 14″ and 16″ duct diameters
- Material
- Galvanized Steel
- Dimensions
- 4″ Duct, 5″ Duct, 6″ Duct, 8″ Duct, 10″ Duct, 12″ Duct, 14″ Duct, 16″ Duct
- Categories
- BalancingConstant Air Volume Dampers
Downloads
Description
SKC-C Series Constant Air Volume Dampers For Circular Duct greatly facilitate the balancing of ventilation systems. Those dampers maintain constant air volume at varying pressures caused by connection and disconnection of system parts, clogging of filters and ducts, wind effects, window opening, etc.
Adjustment is based on the balance of forces on the blade between the air pressure and the reactive forces that exert a spring and an inflatable damper.
The adjustment knob has a graduated rate scale allowing for quick and easy adjustment of the desired air flow. It is located on the outside of the damper, making it easier to adjust the air volume after installation.
Specifications
23 37 XX – Air Balancing Dampers
SKC – High Pressure Constant Air Volume Dampers
Guide specification text for specifiers. The PDF is the reference document.
Read the specificationCollapse
PART 1 – GENERAL
1.1 SUMMARY
A. Section includes supply and installation of constant air volume (CAV) dampers for circular ducts, self-adjustable to maintain a preset airflow rate despite pressure variations.
B. Basis of design: SKC-C constant air volume damper for circular duct, by EffectiV and MADEL.
C. Performance: damper shall maintain preset airflow within system pressure variations from 0.2 to 4.019 in.w.g. (50 to 1,000 Pa).
D. Sizes: available for duct diameters ranging from 4 in to 16 in.
E. Purpose: facilitate air balancing; compensate for pressure changes over time and sudden pressure changes (doors opening, elevators, etc.).
F. Operation: self-adjustable and independent of external energy sources; preset by installer using graduated adjustment knob scale.
G. Post-install adjustment: adjustment knob shall be accessible and re-adjustable from outside the duct after installation, without duct disassembly.
1.2 SUBMITTALS
A. Product Data: manufacturer’s data for each scheduled damper size, including airflow operating range, pressure operating range, and acoustic/pressure loss data.
B. Shop Drawings: show model designation, duct diameter, installed length, airflow direction, installation location(s), and access to the adjustment knob.
C. Balancing/Commissioning Notes: indicate target airflow setpoint(s) and corresponding knob setting(s) for each installed damper, including any post-install readjustment procedure.
1.3 QUALITY ASSURANCE
A. Provide damper(s) from a single manufacturer.
1.4 SUBSTITUTIONS
A. Substitutions per Division 01.
B. Proposed equals shall document compliance with: self-adjusting constant airflow function, stated pressure range, stated size range, no external energy requirement, and post-install re- adjustment capability from outside the duct.
PART 2 – PRODUCTS
2.1 BASIS OF DESIGN
A. EffectiV SKC-C constant air volume damper for circular ducts (EffectiV / MADEL).
2.2 MATERIALS AND CONSTRUCTION
A. Damper construction: galvanized steel.
B. Self-adjusting mechanism: damper shall automatically adjust to maintain preset airflow by balancing air pressure forces with spring/reactive forces.
C. Adjustment: provide graduated adjustment knob scale allowing quick field preset of desired airflow and post-install re-adjustment from outside the duct.
2.3 SIZES AND PERFORMANCE (AS SCHEDULED)
A. Duct diameters: 4 in through 16 in, as scheduled.
B. Operating pressure range: 0.2 to 4.019 in.w.g. (50 to 1,000 Pa).
C. Minimum required pressure differential varies with airflow (per manufacturer data).
PART 3 – EXECUTION
3.1 EXAMINATION
A. Verify duct diameter, installation location, and access to the adjustment knob for setting/verification prior to installation.
3.2 INSTALLATION
A. Install damper in circular ductwork with airflow direction consistent with product airflow marking.
B. Provide minimum straight duct lengths adjacent to damper as indicated by manufacturer installation requirements (minimum 3D upstream and minimum 1.5D downstream).
C. Install with adjustment knob accessible from outside the duct for presetting and future readjustment.
3.3 ADJUSTING AND COMMISSIONING
A. Preset each damper to the scheduled airflow using the graduated knob scale.
B. Verify airflow under representative operating conditions.
C. Where required, re-adjust airflow from outside the duct using the knob setting without duct disassembly.
You might also like
★ KOO
Architectural Adjustable Long Throw Multi-Nozzle Jet Diffuser
Aluminum, Galvanized Steel · Adjustable Airflow
SKP
Low Pressure Constant Air Volume Dampers
10″ Duct, 100 mm, 125 mm, 150 mm, 160 mm, 200 mm, 250 mm, 4″ Duct, 5″ Duct, 6″ Duct, 8″ Duct, 80 mm · UL Rated Plastic
★ PLAY-S
360 Degrees Adjustable Sectors Square Diffuser
24″ x 24″ · Steel
Browse the family
Constant Air Volume Dampers
SKP
Low Pressure Constant Air Volume Dampers
10″ Duct, 100 mm, 125 mm, 150 mm, 160 mm, 200 mm, 250 mm, 4″ Duct, 5″ Duct, 6″ Duct, 8″ Duct, 80 mm · UL Rated Plastic
SKP-HP
High Pressure Constant Air Volume Damper
10″ Duct, 100 mm, 125 mm, 150 mm, 160 mm, 200 mm, 250 mm, 4″ Duct, 5″ Duct, 6″ Duct, 8″ Duct, 80 mm · UL Rated Plastic
SKP-LP
Low Pressure Constant Air Volume Damper
10″ Duct, 100 mm, 125 mm, 150 mm, 160 mm, 200 mm, 250 mm, 4″ Duct, 5″ Duct, 6″ Duct, 8″ Duct, 80 mm · UL Rated Plastic
SelectiV · Verified
Designing a room? Start with the air.
Use SelectiV to lay out diffusers in 3D, or ask for a Verified CFD study to validate comfort, IAQ and energy before anything is installed.