Skip to content

Science · Air changes per hour

ACH counts the room.True ACH counts the people.

Air changes per hour divide the supply airflow by the volume of the room. The figure tells how much air goes in, not where it goes. True ACH is the same figure taken where it matters: in the breathing zone.

True ACH

=

ACH

×

Share delivered to the breathing zone

On the drawings

6ACH

In the breathing zone

True ACH

Warm air supplied and returned at the ceilingSame room, same airflow · sweep across the room

Conceptual illustration only. It shows the principle, not a measurement: real temperatures, airflows and air quality vary from one room, system and building to the next.

What ACH measures

One division, and the room disappears.

ACH is the volume of air supplied in one hour divided by the volume of the room. Its simplicity made it the common language of ventilation. It also treats the room as a tank that mixes perfectly, at every height.

The formula

ACH= 60 × airflow (cfm)volume (ft³)
ACH= 3.6 × airflow (L/s)volume (m³)

Example: 2,000 ft² × 10 ft, supplied with 2,000 cfm: 60 × 2,000 ÷ 20,000 = 6 ACH.Example: 185 m² × 3 m, supplied with 925 L/s: 3.6 × 925 ÷ 555 = 6 ACH.

In the division

  • ✓The supply airflow
  • ✓The room volume

Not in the division

  • ×Where the air goes
  • ×Where the people are
  • ×How well the room mixes

Total supply airflow of the room. Some standards also require a number of outdoor air changes, calculated the same way with the outdoor airflow.

Raise the ceiling. Nothing else changes.

Same floor, same people, same airflow. Only the ceiling moves.

Counted in the ACH Breathing zone

Air changes per hour

Airflow per person

unchanged

Airflow per unit of floor

unchanged

01

It counts air nobody breathes

The volume above the occupants weighs as much in the division as the six feet where they live. A tall room needs more airflow for the same ACH, whether or not that air comes down.

02

It cannot see the path

Supply air that runs along the ceiling to the return, or stays in a warm layer under the roof, counts in full. The ACH is identical whether the air crosses the breathing zone or never reaches it.

03

The return cannot see it either

Whatever the mixing, the air at the return has exactly the nominal age: room volume ÷ airflow. That is a property of every ventilated room. A reading at the return grille will therefore confirm the design ACH even when the occupants get a fraction of it.

True ACH

The air change rate of the breathing zone.

True ACH is the rate at which the air around the occupants is actually replaced by supply air. It is expressed on the same scale as ACH, so the two can be compared, and so can the values the standards publish.

True ACH= ACH× Delivered share

Delivered share. How fast the air of the breathing zone is renewed, relative to a room that mixes perfectly. It is the nominal time constant (volume ÷ airflow) divided by the mean age of air in the breathing zone: the air-change effectiveness that ASHRAE Standard 129 measures, called the local air change index in the ventilation literature.

Estimate

For a first indication, the zone air distribution effectiveness Ez of ASHRAE 62.1, Table 6-4: 0.8 for warm air supplied and returned at the ceiling, 1.0 for cool air supplied at the ceiling. A related factor, not the same measurement.

The Ez factor

Simulate

A CFD study gives the mean age of air at every point of the room, before it is built.

The Verified service

Measure

A tracer-gas test gives the age of air at breathing height in the finished room (ASHRAE 129).

Perfect mixing: True ACH = ACH

The published ACH values assume it. Read as True ACH, they keep their meaning in a room that does not mix perfectly.

The breathing zone, as ASHRAE 62.1 defines it

Between 3 and 72 in (75 and 1800 mm) above the floor and more than 2 ft (600 mm) from the walls or fixed air-conditioning equipment.

A design rule

Size the system so that True ACH, not the nominal ACH, meets the required value. A room that needs 6 and delivers 70 % of its air to the breathing zone needs 8.6 nominal, or a better air distribution.

Mean age of air · Verified simulation

Mean age of air · Verified simulation

From the age of air to the True ACH

What a study returns: the mean age of air at every point of the room, here in seconds. The local air change rate is 3,600 ÷ age: 450 s is 8 air changes per hour at that point, 1,250 s is fewer than 3. True ACH is 3,600 ÷ the mean age of air in the breathing zone.

See it in a room

Same ACH. A different room every time.

A section through a room with ceiling diffusers and a ceiling return. Set the nominal ACH, raise the ceiling and choose how far down the supply air goes. The colours show the local air change rate; the breathing zone carries the True ACH.

Local air change rate, relative to the nominal ACH

‹ 20 % · slower100 % · nominalfaster · › 350 %

Conceptual illustration only. It shows the principle, not a measurement: real temperatures, airflows and air quality vary from one room, system and building to the next. The flow is simplified and two-dimensional; the age of air is then calculated on it the way a CFD code does. It is not a study of your room: a real True ACH comes from a simulation or a measurement.

Nominal ACH

True ACH

Delivered to the breathing zone

Nominal ACH needed for a True ACH of

Calculator

Your room, in ACH and in True ACH.

Enter the room and its supply airflow. Choose the delivered share from the ASHRAE 62.1 defaults or enter the one from a study.

Defaults · ASHRAE 62.1, Table 6-4

Nominal ACH

True ACH

Airflow for the requirement, at this delivered share

The same requirement with perfect mixing

ACH = hourly supply airflow ÷ (area × height). True ACH = ACH × delivered share. The Table 6-4 values are defaults for ventilation air, defined on contaminant concentration: they are used here as a first indication only. A CFD study or a tracer-gas test gives the value of the room.

Reference values

The published air change rates, in one place.

Selected values from the standards and guidelines that prescribe or cite air changes. Each is written for a room that mixes perfectly. Set the delivered share to read what the nominal figure must be for the True ACH to meet it.

SpaceTotal ACH requiredof which outdoor airNominal ACH to supply
Patient room42
Critical and intensive care62
Newborn intensive care62
Operating room204
Procedure room153
Bronchoscopy122
Airborne infection isolation (AII) room122
Protective environment (PE) room122
Emergency department exam or treatment room62
Emergency department public waiting area122
General examination room42
Laboratory work area, general62
Pharmacy42
Toilet room (exhausted)10–

Minimum air changes for inpatient spaces; the patient room was 6 in the 2008 edition. A 2025 edition has been published. Standard 170 already reasons on the occupied volume in one case: for single-bed patient rooms with Group D diffusers, the 2017 edition as amended asks for six air changes calculated on the volume from the floor to 6 ft (1.83 m). Selected rows, for orientation. The standard governs: check the current edition, its addenda and the code adopted in your jurisdiction. Source: ANSI/ASHRAE/ASHE Standard 170-2021 with addenda, Table 7-1.

Common questions

ACH, in short.

How do you calculate air changes per hour?

Multiply the supply airflow in cfm by 60 and divide by the room volume in cubic feet (in metric: L/s × 3.6 ÷ m³). A 2,000 ft² room with a 10 ft ceiling supplied with 2,000 cfm has 6 air changes per hour.

What is True ACH?

The air change rate in the breathing zone: the nominal ACH multiplied by the share of that air renewal that reaches the occupants. With perfect mixing it equals the ACH; with stratification or short-circuiting it is lower.

Is a higher ACH always better?

Not by itself. Moving more air through a room that stratifies or short-circuits mostly raises fan and conditioning energy. Delivering the same air to the breathing zone raises the True ACH without more airflow.

Does True ACH replace the ACH required by a code?

No. Where a code or a standard prescribes air changes, that value must be met as written. True ACH is a design check on top of it: it tells whether the occupants actually receive the air change rate the requirement intends.

Read next

Where the air goes, everything else follows.

SelectiV · Verified

Designing a room? Start with the air.

Use SelectiV to lay out diffusers in 3D, or ask for a Verified CFD study to validate comfort, IAQ and energy before anything is installed.